Horizontal Rooftop Packaged Unit

Short Description:

Bueco rooftop packaged units are applied in the industrial and commercial fields such as hotel, supermarkets, authorized dealing shop, office building and factory workshop. They perfectly connect many characteristic of large-sized central a/c, such as convenience, comfort, high-class , the simplicity and flexibility. The new design makes use of the space module, the features of small-sized commercial modern building space, making the cool and heat air spread into each room averagely to form...


  • FOB Price: To be quoted
  • Min.Order Quantity: 1
  • Port: Tianjin
  • Payment Terms: TT, L/C
  • Product Detail

    Product Tags

    23444556666 app

    Bueco rooftop packaged units are applied in the industrial and commercial fields such as hotel, supermarkets, authorized dealing shop, office building and factory workshop. They perfectly connect many characteristic of large-sized central a/c, such as convenience, comfort, high-class , the simplicity and flexibility. The new design makes use of the space module, the features of small-sized commercial modern building space, making the cool and heat air spread into each room averagely to form “Zero” temperature difference. Besides, outdoor fresh air can be absorbed. The air path can connect with indoor ornament which is completely hidden and does not occupy any space. It has become a new generation of products of central a/c and traditional commercial a/c.

    fea

    1. Various products and wide application

    The series of Rooftop units include many different specifications which can completely meet the demand of home and commercial places and offer you a comfortable and pleasant environment.

    2. Complete air system, simple and hygiene, less components, easy maintenance

    The flexible and concise design makes the maintenance very simple. Disassembling several bolts from any side of the unit can repair any part of the unit.

    3. Microcomputer intelligent controller

    It can reach control modes: cooling, heating, ventilation and optional free cooling. It also has the functions of timing on-off and failure display.

     1234454

    4. Excellent performance

    World well-known brand of main parts are used. To guarantee the rational match of the unit, strict performance testing is done. Besides the unit runs steady and the vibration and noise are effectively controlled by the use of multi-vane pitch centrifugal fan, world-known high efficiency compressor and the elaborative-designed controller, motor, etc.

    $66$J_L_943@UHD5AQR$RKB 23124134325432 4523543546

    5. Quiet operation and Convenient maintenance

    Reach the lowest noise of the a/c room. The a/c units are placed far from the a/c area which meets the demand of indoor low noise to the greatest degree. The adoption of high efficiency and low noise centrifugal fan makes the quiet operation come true.

    op

    Free cooling

     32132142354654675

    Free cooling logic:

    1. When it is heating, the fresh air damper is closed, and return air damper is 100% open;

    2. When it is cooling:

          a. When indoor room temperature (temperature set) – outdoor temperature ≥ 4 ℃,fresh air damper is 100% open, and return air damper is 100% closed,only the evaporator fan is running to blow air into room;

          b. When 0 ℃ ≤ indoor room temperature (temperature set) – outdoor temperature< 4 ℃ ,both fresh air damper and return air damper are closed, and the unit is not running;

          c. When indoor room temperature ( temperature set) – outdoor temperature < ℃,the return air damper is 100% open,and fresh air damper is 100% closed,then the compressor, condensing fan and evaporator fan will work normally to blow cool air into room.

    Heat recovery

    Bueco heat recovery fresh air unit turns the silent building into a house with aspiration function, all the pollutant such as smoke, dust and odor etc. will be cleared with the exhaust and supply air system, so the indoor air quality is clean and comfortable. The city residents spend their time more than 90% in room, the air-conditioned room air quality is critical to health. Bueco heat recovery fresh air unit becomes the “lung” of modern building practically, it is a new fresh air healthy and environment friendly product.

    The application of nano film technology, horizontal reverse counter flow technology, antistatic & maintenance free technology and attenuation technology, Bueco solved the low efficiency problem of traditional heat recovery unit, total heat recovery efficiency up to 75%. The heat recovery fresh air unit reduces the air conditioning load, initial investment and system operation cost.

    se

    Table 1

    Model

    BRPN36

    BRPN48

    BRPN60

    BRPN72

    BRPN96

    BRPN125

    Cooling Capacity

    kW

    12

    15.2

    17.5

    24

    30.3

    35.6

    Heating Capacity

    kW

    13.2

    16.6

    18.4

    26.5

    33.3

    37.7

    Cooling Input

    kW

    4.1

    5.3

    5.5

    8.8

    11.3

    12.3

    Heating Input

    kW

    3.8

    4.8

    5.1

    8.2

    10.4

    11.3

    Circuit number

    Nos.

    1

    1

    1

    2

    2

    2

    Start current

    A

    48

    62

    63

    63

    74

    76

    Cooling operation current

    A

    7.4

    9.7

    10.2

    16.1

    21.2

    23.3

    Heating operation current

    A

    6.9

    9.2

    9.7

    15.1

    20.1

    22.2

    Power

    V/Ph/Hz

    380/3/50 60Hz Optional

    Compressor

    Type

    Hermetic Scroll Compressor

    Cond. fan

    Type

    Direct driven axial fan

    Supply fan

    Type

    Direct driven centrifugal fan

    Belt driven centrifugal fan

    Air flow

    m3/h

    2100

    2600

    3400

    4100

    5200

    6300

    Max ESP

    Pa

    100

    100

    100

    200

    200

    250

    Filter type

     

    Aluminum G3

    Noise

    dB(A)

    67

    67

    68

    71

    72

    72

    Refrigerant

    Type

    R410A

    Refri. charge amount

    Kg

    3.1

    3.1

    4.3

    2×3.1

    2×3.1

    2×4.3

    Dimension(mm)

    Length

    1410

    1410

    1410

    1978

    1978

    1978

    Width

    1100

    1100

    1100

    1175

    1175

    1175

    Height

    1095

    1095

    1095

    1095

    1095

    1095

    Weight

    Kg

    240

    260

    290

    420

    480

    500

     

    Table 2

    Model

    BRPN168

    BRPN180

    BRPN210

    BRPN250

    BRPN300

    BRPN360

    Cooling Capacity

    kW

    44.5

    50

    60

    70

    90

    105

    Heating Capacity

    kW

    48.7

    54.3

    64

    75.4

    96.2

    113.2

    Cooling Input

    kW

    17

    19.5

    22.8

    26.7

    32.9

    39.7

    Heating Input

    kW

    15.6

    18

    21

    24.8

    30.4

    36.7

    Circuit number

    Nos.

    2

    2

    2

    2

    3

    3

    Start current

    A

    168

    186

    175

    199

    197

    266

    Cooling operation current

    A

    31.7

    35.6

    39.9

    48.3

    61

    70.6

    Heating operation current

    A

    29.9

    33.5

    37.5

    45.4

    57.3

    66.3

    Power

    V/Ph/Hz

    380/3/50 60Hz Optional

    Compressor

    Type

    Hermetically Sealed Scroll Compressor

    Cond. fan

    Type

    Direct driven axial fan

    Supply fan

    Type

    Belt driven centrifugal fan

    Air flow

    m3/h

    7600

    8500

    10900

    12500

    16000

    19500

    Max ESP

    Pa

    250

    250

    300

    300

    300

    300

    Filter type

     

    Aluminum G3

    Noise

    dB(A)

    73

    73

    73

    75

    74

    75

    Refrigerant

    Type

    R410A

    Refri. charge amount

    Kg

    6.3+3.5

    4.3+8.5

    2×7.5

    2×8.5

    3×7.5

    3×8.5

    Dimension(mm)

    Length

    2268

    2268

    2298

    2298

    2878

    2878

    Width

    1440

    1440

    1650

    1650

    2140

    2270

    Height

    1167

    1167

    1400

    1400

    1964

    1964

    Weight

    Kg

    750

    770

    830

    860

    1160

    1350

    Table 3

    Model

    BRPN415

    BRPN480

    BRPN520

    BRPN630

    BRPN750

    BRPN1023

    Cooling Capacity

    kW

    120

    140

    149

    180

    210

    298

    Heating Capacity

    kW

    128.3

    150

    159.2

    192.5

    226

    318

    Cooling Input

    kW

    45.1

    55.7

    55.1

    69.9

    83

    106.7

    Heating Input

    kW

    41.7

    51.8

    51.5

    64.8

    77

    100

    Circuit number

    Nos.

    4

    4

    2

    6

    6

    4

    Start current

    A

    218

    252

    323

    232

    301

    415

    Cooling operation current

    A

    82.4

    101.4

    100.2

    130.9

    151

    192.3

    Heating operation current

    A

    77.4

    95.7

    95.1

    123.5

    142.3

    184.3

    Power

    V/Ph/Hz

    380/3/50 60Hz Optional

    Compressor

    Type

    Hermetically Sealed Scroll Compressor

    Cond. fan

    Type

    Direct driven axial fan

    Supply fan

    Type

    Belt driven centrifugal fan

    Air flow

    m3/h

    21000

    25000

    26000

    32000

    38000

    54000

    Max ESP

    Pa

    400

    400

    400

    500

    500

    500

    Filter type

     

    Aluminum G3

    Noise

    dB(A)

    75

    79

    79

    80

    80

    82

    Refrigerant

    Type

    R410A

    Refri. charge amount

    Kg

    4×7.5

    4×8.5

    2×17

    6×7.5

    6×8.5

       4×14

    Dimension(mm)

    Length

    3626

    3626

    3626

    4690

    4690

    5660

    Width

    2200

    2200

    2200

    2330

    2330

    2330

    Height

    2047

    2047

    2047

    2055

    2055

    2055

    Weight

    Kg

    1710

    1820

    1850

    2180

    2430

    2860

    NOTES:  

    1. Cooling conditioning: Indoor temperature DB: 27 ℃, WB: 19 ℃; outdoor temperature DB: 35 ℃,WB: 24 ℃.
    2. Heating conditioning: Indoor temperature DB: 20 ℃, WB: 15 ℃; outdoor temperature DB: 7 ℃,WB: 6 ℃.