Modular Scroll Air Cooled Water Chiller

Short Description:

This series of scroll air cooled water chiller is for room air conditioning with fan coil unit or air handling unit or industrial factory process cooling with the chilled water. If you have any preference of the compressor brand, please inform. If there is any different requirement other than the standard product, please inform, will have customization upon request. Unique design, higher COP, less investmentModular design suitable for bigger application area, automatic energy output adj...


  • FOB Price: To be quoted
  • Min.Order Quantity: 1
  • Port: Tianjin
  • Payment Terms: TT, L/C
  • Product Detail

    Product Tags

    1231231

    app

    This series of scroll air cooled water chiller is for room air conditioning with fan coil unit or air handling unit or industrial factory process cooling with the chilled water. If you have any preference of the compressor brand, please inform. If there is any different requirement other than the standard product, please inform, will have customization upon request.

    fea

    Unique design, higher COP, less investmentModular design suitable for bigger application area, automatic energy output adjustment as per actual load requirement, operation cost is 15% less than screw type air cooled water chiller.Multi steps start by sequence, minimize starting current, safe to electricity grid.Full parallel scroll compressor technique, COP 7% higher than screw chiller in full load, and 15% to 20% higher in partial load. 213213
    Fully-automatic controlThe operation and management of this unit are controlled by microcomputer system. It is easy to operate. The units turn on/off the compressor automatically according to the load, making the units operate on the point of the most economical and energy saving. And there are complete protective functions such as error self-protection system and anti-freezing automatically in winter. 13213

    Intelligent defrosting 

    Each circuit is separate to the others in refrigerant system, and each system operation is controlled independently.  The parameters can be set for automatic defrosting according to the different climatic conditions (temperature and humidity), defrost is thorough and energy-saving, increasing the heating efficiency. And the defrosting has no significant influence to the indoor air-conditioning temperature. 

    Convenient operation

    Each unit is strictly tested. All the protective parameters is set.  It is ready for application right after the power supply and water pipe is connected.

    op

    1. Heat recovery for domestic hot water

    2. Water flow switch  

    3. Touch screen or PLC controller

    4. R134A refrigerant  

    5. For any other feature, please contact us for customization 

    se

    Table 1

    Model

     

    BMA65

    BMA85

    BMA100

    BMA130

    BMA160

    BMA200

    Power

    V-Ph-Hz

    380-415,3,50

    Cooling

    Capacity

    kW

    65

    85

    97.5

    130

    168

    197

    Power input

    kW

    21

    28.4

    31.7

    41.4

    53.3

    62.6

    Current

    A

    36.90

    50.9

    55.1

    73.40

    94.00

    109.70

    EER

    kW/kW

    3.10

    2.99

    3.08

    3.14

    3.15

    3.15

    MAX power input

    kW

    25.2

    34.1

    38.0

    49.7

    64.0

    75.1

    MAX current input

    A

    44.3

    61.1

    66.1

    88.1

    112.8

    131.6

    Start-up current  

    A

    146.0

    152.0

    171.0

    189.0

    319.0

    334.0

    Compressor

    Type

     

    Scroll

    Scroll

    Scroll

    Scroll

    Scroll

    Scroll

    Power input

    kW

    2×9.7

    3×8.8

    3X9.7

    4×9.7

    2×20.4+8.3

    2×20.4+2×8.3

    Running current

    A

    2×19.01

    3×15.2

    3X16.6

    4×16.6

    2×35.4+14.6

    2×35.4+2×14.6

    Refrigerant Type

     

    R410A

    R410A

    R410A

    R410A

    R411A

    R411A

    Refrigerant amount

    kg

    2×8.6

    3×8.6

    3X8.6

    4×8.6

    2×18+8.6

    2×18+2×8.6

    Axial condensing fan

    Quantity

    Nos.

    2

    2

    2

    2

    4

    4

    Air flow

    m3/h

    24000

    36000

    36000

    48000

    58000

    68000

    Power input

    kW

    0.75×2

    1.5+0.75

    1.5+0.75

    1.5×2

    2×1.1+2×0.75

    4×1.1

    Expansion valve type

     

     Electronic expansion

    Axial condensing fan

    Type

     

    Shell and tube type

    Water flow

    m3/h

    10.32

    15.1

    18.6

    22

    29

    33.9

    Water pressure drop

    kpa

    42

    42

    41

    41

    45

    45

    Water pipe connection in/out

    mm

    DN50

    DN50

    DN50

    DN65

    DN80

    DN100

    Noise

    dB(A)

    70

    72

    72

    75

    75

    75

    Dimension

    L

    mm

    2000

    2240

    2240

    2240

    2400

    2488

    W

    mm

    1060

    1360

    1360

    1360

    1200

    2207

    H

    mm

    1865

    1926

    1926

    1926

    2315

    1988

    Net weight

    kg

    640

    990

    1060

    1120

    1760

    2160

     Table 2

    Model

     

    BMA210

    BMA280

    BMA340

    BMA410

    BMA480

    BMA550

    Power

    V-Ph-Hz

    380-415,3,50

    Cooling

    Capacity

    kW

    204

    272

    340

    408

    476

    544

    Power input

    kW

    66.1

    88.3

    110.3

    132.5

    154.5

    176.6

    Current

    A

    115.7

    155.7

    193.6

    233.5

    271.4

    311.4

    EER

    kW/kW

    3.08

    3.08

    3.08

    3.08

    3.08

    3.08

    MAX power input

    kW

    79.4

    106.0

    132.4

    159.0

    185.4

    212.0

    MAX current input

    A

    138.9

    186.8

    232.3

    280.2

    325.7

    373.6

    Start-up current  

    A

    340.3

    380.2

    418.1

    458.1

    496.0

    535.9

    Compressor

    Type

     

    Scroll

    Scroll

    Scroll

    Scroll

    Scroll

    Scroll

    Power input

    kW

    4×20.4

    4×20.4

    5×20.4

    6×20.4

    7×20.4

    8×20.4

    Running current

    A

    4×35.4

    4×35.4

    5×35.4

    6×35.4

    7×35.4

    8×35.4

    Refrigerant Type

     

    R410A

    R411A

    R411A

    R411A

    R411A

    R411A

    Refrigerant amount

    kg

    3×18

    4×18

    5×18

    6×18

    7×18

    8×18

    Axial condensing fan

    Quantity

     

    3

    4

    6

    6

    8

    8

    Air flow

    m3/h

    76000

    96000

    120000

    144000

    168000

    192000

    Power input

    kW

    2×2.2+

    2×0.75

    4×1.5

    4×1.5+

    2×0.75

    6×1.5

    6×1.5+

    2×0.75

    8×1.5

    Expansion valve type

     

     Electronic expansion

    Axial condensing fan

    Type

     

    Shell and tube type

    Water flow

    m3/h

    35

    46.8

    58.5

    70.2

    82

    93.6

    Water pressure drop

    kPa

    48

    48

    47

    50

    48

    50

    Water pipe connection in/out

    mm

    DN100

    DN125

    DN125

    DN150

    DN150

    DN150

    Noise

    dB(A)

    76

    76

    76

    76

    77

    77

    Dimension

    L

    mm

    2488

    2550

    3340

    3640

    4330

    4730

    W

    mm

    2207

    2206

    2206

    2206

    2206

    2206

    H

    mm

    2050

    2465

    2465

    2465

    2465

    2465

    Net weight

    kg

    2450

    2450

    2950

    3200

    4150

    4520

    Notes:

    1.  Standard cooling work condition: Ambient Temp: DB 35 ℃, WB 24 ℃; cooling water inlet 12 ℃, outlet 7 ℃.
    2.  The noise data is measured on the average of 1m far away from the unit.
    3.  Reserve the right to change the parameter without prior notice.  
    4.  Water side max. bearing pressure: 1.0 MPa.


  • Previous:
  • Next:

  • WhatsApp Online Chat !